积分器
锁相环
控制理论(社会学)
计算机科学
电压
相(物质)
逆变器
电子工程
网格
拓扑(电路)
工程类
数学
相位噪声
物理
几何学
控制(管理)
量子力学
人工智能
电气工程
组合数学
作者
Mihai Ciobotaru,Remus Teodorescu,Frede Blaabjerg
标识
DOI:10.1109/pesc.2006.1711988
摘要
Phase, amplitude and frequency of the utility voltage are critical information for the operation of the grid-connected inverter systems. In such applications, an accurate and fast detection of the phase angle, amplotude and frequency of the utility voltage is essential to assure the correct generation of the reference signals and to cope with the new upcoming standards. This paper presents a new phase-locked-loop (PLL) method for single-phase systems. The novelty consists in generating the orthogonal voltage system using a structure based on second order generalized integrator (SOGI). The proposed structure has the following advantages: — it has a simple implementation; — the generated orthogonal system is filtered without delay by the same structure due to its resonance at the fundamental frequency, — the proposed structure is not affected by the frequency changes. The solutions for the discrete implementation of the new proposed structure are also presented. Experimental results validate the effectiveness of the proposed method.
科研通智能强力驱动
Strongly Powered by AbleSci AI