Criterion Based on the Fault Component of Zero Sequence Current for Online Fault Location of Single-phase Fault in Distribution Network
作者
Yang Yi-han
摘要
When single-phase earthing fault occurs,the resonant grounded system could keep on running for 1 or 2 hours. If the fault is removed during this period,power will be continuously supplied to the distributed network system. In order to deal with the problem proposed above,a new online fault location criterion was proposed using zero-sequence current difference through analyzing the characteristic of the branch fault on substation outlet,the branch fault on non-outlet,and the characteristic of the fault component of zero sequence current. By this criterion,the single-phase earthing fault in resonant earthing distributed network can be located online. ATP simulation results demonstrated the correctness and validity of the criterion.