Eddy Current versus Joule Heating Effects for a Cable Suspended in an Iron Pipe
作者
Prashobh Karunakaran,M. Shahril Osman,V. Karuppanna,Sung Chee Cheng,Man Djun Lee,Muhd Dina Fadhilah,A. K. S. Lau
出处
期刊:2020 IEEE International Conference for Innovation in Technology (INOCON)日期:2020-11-06卷期号:: 1-6被引量:2
标识
DOI:10.1109/inocon50539.2020.9298438
摘要
The aim of this research is to prove that when a current carrying cable is suspended at the center of a steel pipe, eddy current is the main energy loss and not joule heating or I 2 R loss. Various experiments were done, sending currents levels of between 54A to 108A in a twisted bare Cu cable or PVC insulated cables within steel and HDPE pipes. The heat loss was measured with two heat measuring instruments which enabled a conclusion to be formed that most of the energy loss is due to eddy current and not Joule heating. As long as the cable is sized higher than the current carrying capacity, there will be negligible Joule heating and the main loss will be eddy current loss.