Effect of Operational Conditions on Cooling Performance of Pump-Assisted and Capillary-Driven Two-Phase Loop
作者
Michael Crepinsek,Chanwoo Park
出处
期刊:2018 AIAA Aerospace Sciences Meeting [American Institute of Aeronautics and Astronautics] 日期:2011-01-04被引量:1
标识
DOI:10.2514/6.2011-811
摘要
As electronics advance and utilize higher power densities, the demand for efficient cooling methods increase. Because of high heat flux capability, two-phase cooling systems may be applied to cool a wide variety of newly emergent technologies such as power electronics seen in electric-drive vehicles. This paper presents the experimental results of the cooling performance of a pump-assisted and capillary-driven two-phase loop which utilizes a unique planar evaporator. The evaporator is fed liquid by both mechanical and capillary pumping, while the vapor and liquid phases in the evaporator are separated by capillary force to prevent it from flooding. Water was used as the working fluid. To reduce the heat leakage through the wall of the evaporator, stainless steel of a relatively low thermal conductivity was used as evaporator enclosure material, while copper was used for the heater. This paper discusses the effects of various operation variables of the two-phase cooling loop, such as heat input, system pressure, liquid flow rate, and heat sink temperature on the cooling performance of the two-phase loop.