Auto-cascade refrigeration (ACR) systems are widely used at low temperatures. The selection and ratio optimization of zeotropic refrigerants in ACR systems have an important impact on system performance and environmental protection. This study proposes a three-stage regenerator-enhanced auto-cascade refrigeration (RACR) system. Under certain working conditions, the theoretical performances of the three-stage R134a/R23/R14 ACR and RACR systems were compared, and the influence of the refrigerant mixture ratio on the RACR system performance was explored. The system performances of replacing R134a and R23 with different hydrocarbons were compared under different working conditions. The results demonstrated that RACR performed better than ACR alone. A reasonable adjustment to the mixed refrigerant ratio improved the energy efficiency of the RACR system. Water-cooling conditions for the RACR system were suggested, under which the coefficient of performance, thermodynamic perfectness, and exergy efficiency of R600/R170/R14 were 13.8 %, 12.4 %, and 8.4 % higher than those of R600/R23/R14, respectively. The environmental policy, safety requirements, and energy efficiency were considered to obtain −100 °C, R600/R170/R14 with mass fractions of 0.24/0.12/0.64 was the best choice in a water-cooled RACR system.