In general the problem of reactive power control is viewed from two aspects: load compensation and voltage support. This is utilized to reduce the total system real power loss or voltage deviation as an objective to compute optimal settings of reactive power output or terminal voltages of generating plants, transformer tap settings and output of other compensating devices such as capacitor banks and synchronous condensers. This paper has considered the setting of flexible AC transmission system (FACTS) devices as additional control parameters for transmission loss reduction in power system and the impact on system loss reduction in power system. Static models of two FACTS devices consisting of static var compensator (SVC), thyristor controlled series compensator (TCSC) have been included in the problem formulation. The proposed algorithm has been applied to 9-bus test system and IEEE 14-bus system. Keyword: Reactive power, Newton- Raphson technique, SVC, TCSC