定子
电磁线圈
故障指示器
对称分量
断层(地质)
泄漏(经济)
工程类
接地
电压
剩余电流装置
控制理论(社会学)
电气工程
故障检测与隔离
计算机科学
变压器
断路器
控制(管理)
人工智能
地震学
地质学
经济
执行机构
宏观经济学
作者
Yuan Yuan Wang,Xiang Jun Zeng,Jin Jian,Zhao Yang Dong,Ze Wen Li,Yue Huang
标识
DOI:10.1109/tec.2013.2240303
摘要
A new criterion to detect the stator single-phase-to-ground fault for Powerformer is proposed in this paper, which is based on the direction of leakage currents, magnitude of leakage currents, and fault point energy dissipation. New fault characteristics of Powerformer are analyzed and a novel criterion is put forward. The proposed approach detects the ground fault by analyzing the direction, magnitude, and energy of leakage current, which is the difference of zero-sequence current fault component between the neutral and the terminal of Powerformer. The fundamental component and the third-harmonic component of leakage current are combined to realize 100% coverage of fault detection for the stator windings of Powerformer. Simulation results have shown that, under different fault conditions, the new scheme can distinguish internal faults from external faults reliably, and can detect in which machine a stator single-phase-to-ground fault is occurring even if the fault resistance is at 5 kΩ.