计算流体力学
冷却塔
塔楼
海洋工程
阻力
流利
仪表(计算机编程)
工程类
模拟
气象学
水冷
机械工程
计算机科学
航空航天工程
结构工程
物理
操作系统
作者
Nicolas Blain,Antoine Belaud,Matthieu Miolane
标识
DOI:10.1016/j.applthermaleng.2016.03.020
摘要
Électricité de France (EDF) has commissioned the development of a CFD model, based on ANSYS Fluent v.16, which includes the specific equations (Poppe and Merkel) describing the physical phenomena occurring in a natural draft wet cooling tower (NDWCT). Heat and mass transfers between water and air, as well as drag equations for the two-phase system, are computed in specific zones such as the cooling fill, spray and rain zones. This paper presents the CFD model created and the two-step methodology implemented for the validation process: The model is first tested and set regarding thermal performance results obtained on EDF test cell Mistral located on the Bugey site. The Mistral facility includes a 7 m × 7 m counter-flow section, equipped with a large number of temperature and pressure sensors, which represents an efficient and reliable mean for cooling fill performances evaluation. Secondly, the model is fully validated thanks to acceptance tests results gathered from a large scale NDWCT refurbishment. To this end, advanced instrumentation was positioned in the tower to provide additional data for extensive validation of the model.
科研通智能强力驱动
Strongly Powered by AbleSci AI