Bryony Watson,Julien de Charentenay
出处
期刊:Building Simulation Conference proceedings
日期:2020-06-23
卷期号:16: 600-607
标识
DOI:10.26868/25222708.2019.210349
摘要
Air cooled chillers serving high building cooling loads such as data centre are prone to air re-entrainment.As air re-entrainment is deemed to be specific to each project, it is customary to either ignore it or allow a nominal amount based on past experience at concept stage.This parametric study uses Computational Fluid Dynamics (CFD) to evaluate principal components affecting air re-entrainment within air-cooled chiller compounds.Results shows that air re-entrainment increases with wind speed and that at highest wind speed air re-entrainment is linearly dependent on plant compound length.These linear relationships, which are deemed to be adequate for plant compound with heat rejection density between 15 and 25kW/m 2 , can be applied at concept design to provide an early estimate of air re-entrainment.