Yuhao Xie,Xinchen Zou,Mengzhao Duan,Feilong Fan,Haoyu Wang,Yu Liu
标识
DOI:10.1109/tie.2025.3577310
摘要
For lines terminated by inverter based resources (IBRs), the performance of the legacy distance relay could be affected by the characteristics of IBRs during faults. Improved distance relays in the existing literature often rely on communication from the remote end or specific IBR control strategies, limiting the compatibility of these relays. This article proposes a distance protection method at the IBR side of the line. First, the sequence equivalent circuits of IBRs are treated as three unavailable boxes. Next, the proposed method combines the information within multiple the sequence networks, to accurately consider the impact of fault resistance and remote end infeed current. Finally, the unknown fault distance is analytically solved as a root of the quadratic equation. The proposed method does not have specific assumption on IBR control schemes, step-up transformer winding connections, or branches at the local bus, and can therefore work in power systems with various grid codes. Moreover, the proposed method is compatible with present phasor data acquisition systems at local terminal and does not require remote end information. Simulations, hardware experiments and field data experiments demonstrate the effectiveness of the proposed distance protection.