电弧闪光
电压
电阻抗
等效电路
波形
等效阻抗变换
材料科学
电气工程
电子工程
声学
工程类
物理
作者
Mohammed El Amine Slama,Abderrahmane Béroual,A. Haddad,Maurizio Albano
标识
DOI:10.1109/tdei.2022.3175152
摘要
This paper introduces a complementary criterion for flashover (FOV) of polluted insulators based on the concept of equivalent impedance variation with discharge length and leakage current. An analytical electro-thermal model enabling the calculation of critical flashover voltage and critical current of polluted insulators is developed using this complementary criterion and the equivalent impedance criterion. It is shown that the critical parameters depend on the thermal characteristic of the discharge and the components of the equivalent electrical circuit. The comparison of the computed FOV voltage and critical current are in good accordance with the experimental ones for a laboratory insulation flat sample model with different applied voltage waveforms. The application of the developed model to actual insulators destined for 11kV systems, by including ESDD and the form factor show that FOV voltage values match very well with the experimental data in clean fog test conditions.
科研通智能强力驱动
Strongly Powered by AbleSci AI