In energy-retrofit projects for in-service (existing) data centers, a pronounced vertical elevation difference often exists between the heat-rejection end and the server room, and the retrofit must typically be implemented under online (no-downtime) conditions. Taking an in-service existing data center as the case study, this work upgrades the legacy cooling architecture to a pump-driven two-phase backplate cooling system for near-end thermal management while ensuring service continuity, and establishes a pPUE metric and a corresponding measurement boundary suitable for partial-retrofit scenarios. Four months of continuous field measurements show that, under an approximately 20m vertical elevation difference, the system operates stably and maintains the server-room temperature at 24.5±0.5°C under dynamic load disturbances. Benefiting from the high latent heat of vaporization of the working fluid and the incorporation of a vapor–liquid separator, the system mitigates the energy penalty typically associated with long-distance transport, yielding a cumulative pPUE as low as 1.20 over the monitoring period. These results demonstrate the engineering adaptability and superior energy performance of the proposed technology in complex, space-constrained retrofit settings, and provide a practical reference for the green and low-carbon transition of data infrastructure.