开关设备
电气工程
湿度
分析化学(期刊)
材料科学
化学
工程类
物理
有机化学
热力学
作者
Yuyou Long,Feng Zhu,Shixin Xiu,Fengxiang Ma,Zepeng Chen,Zhenxi Su
标识
DOI:10.1109/icepe-st.2019.8928852
摘要
Sulfur hexafluoride (SF6) has excellent insulating and arc quenching properties, but it has strong greenhouse effect which is 23900 times of CO2. Nitrogen (N2) is an environmental-friendly gas with good insulation performance and is developed to use in gas insulated equipment in recent years. In this paper, the effect of humidity and purity on N2insulated switchgear was researched. A 40.5 kV N2insulated switchgear was taken as the test object. Short-duration power-frequency withstand voltage test and lightning impulse voltage test were carried out under different gas purity and humidity. The test results showed that N2 mixed with 20% O2can pass both tests. N2containing 650 ppm, 1200 ppm and 2380 ppm water can pass both tests. While the water content increased to 12700 ppm, the switchgear cannot pass the test. From the aspects of ionization energy and electronegativity, the test results were analyzed. The results can provide guidance and basis for the maintenance and operation of N2insulated switchgears.
科研通智能强力驱动