爆燃转爆轰
起爆
易燃液体
爆炸物
材料科学
燃烧
机械
火焰蔓延
压力波
核工程
点火系统
火焰速度
工程类
结构工程
预混火焰
废物管理
法律工程学
化学
燃烧室
航空航天工程
有机化学
物理
作者
Lei Bao,Peng Wang,Wenyi Dang,Kuang Chen,Anfeng Yu
标识
DOI:10.1016/j.jlp.2021.104529
摘要
Abstract In-line detonation flame arresters are important safety apparatus to prevent group tank fires caused by the spreading of fire through vapor connection lines. In this study, a DN50 experimental apparatus aimed at the detonation flame penetration characteristics and failure mechanisms in a flame arrester was set up, and a series of experiments were carried out with 6.6% C2H4 and air mixture. Pressure, and velocity of flame penetrating through flame arrester housing and filters were analyzed. Experimental results showed that the attenuation of pressure and velocity was proportional to the thickness of the filters. Two failure modes of the fire-extinguishing process in the flame arrester were captured directly with a high-speed camera. In Mode I, the detonation flame could go straight through the flame arrester filters when the filters were too thin. In Mode II, when the filters were not sufficiently thick, the remained shock wave pressure of detonation flame was still several times of the initial pressure and could rise sharply at the downstream contraction section, resulting in that the flammable gas at the downstream transition section could be compressed and reignited even the flame had been extinguished by filters. These conclusions are helpful to reveal the nature of failure modes of fire-extinguishing process and design flame arresters with high fire-resisting performance by structure improved.