腐蚀
断裂(地质)
结构工程
塔楼
材料科学
微观结构
腐蚀疲劳
输电线路
输电塔
拱门
复合材料
工程类
电气工程
作者
Hao Chen,Xuechao Zhang,Xiao Liu,Xin Qiao
标识
DOI:10.1051/e3sconf/202016506005
摘要
The guyed rod is of great importance for supporting tower and resisting wind pressure, and its reliability is an effective guarantee for safe and stable operation of power grid. In this paper, the fractured guyed rod used for cable stayed iron tower in a 110kV transmission line was investigated by means of macro-morphology inspection, chemical composition analysis, microstructure analysis, scanning electron microscope, mechanical properties test, soil physicochemical properties inspection and energy spectrum analysis. The result showed that electrode potentials difference existed between different parts on the surface of the guyed rod caused by the uneven distribution of oxygen concentration was the major reason for electrochemical corrosion. Under the action of oxygen concentration cell, the effective cross-sectional area of the guyed rod decreased below the critical value, leading to the final fracture of the guyed rod.