期刊:Journal of vinyl technology [Wiley] 日期:1988-06-01卷期号:10 (2): 84-89被引量:1
标识
DOI:10.1002/vnl.730100208
摘要
Abstract The conventional test method for evaluating the potential of a material to produce smoke in a real fire is the NBS Smoke Density Chamber. However there are major problems with this approach. These include foremost the fact that its results do not correlate with those of real fires. Furthermore, materials that melt and drip are able to achieve a favorable, but misleading, evaluation because a significant fraction of the sample escapes the burning process. Another problem is that the test takes no account of the role the rate or extent of material burning plays in controlling the smoke density in a real fire situation. The physical problems are solved by material smoke production evaluation techniques based on measurements from the Cone Calorimeter rate of heat release apparatus, which has been developed by the National Bureau of Standards. A smoke parameter has been developed, calculated from cone calorimeter measurements, which reflects the smoke hazard of a real fire. The smoke evolution characteristics for a series of rigid thermoplastic materials have been measured using the cone calorimeter and the smoke parameter concept. The results demonstrate that due to its tendency to resist ignition and to burn very slowly, PVC would produce very little smoke in a real fire situation. Of the 15 materials tested, the expected real fire smoke performance characteristics of PVC were superior to those of all other materials except one.