The technology of on-Line detection of composite Insulator of ±800 kV UHVDC transmission line was researched and a harmonic electric field detector was developed based on F040.The results of laboratory test and on-site test demonstrated that longitude harmonic electric field distribution both in healthy insulator and in failure insulator complies with the requirement of general electric field detection principle and that harmonic electric field detection can be used for the detection of inner insulation defect in composite insulator of 800 kV UHV DC transmission line.