模块化设计
断层(地质)
电流(流体)
控制(管理)
控制理论(社会学)
计算机科学
工程类
电气工程
操作系统
地质学
人工智能
地震学
作者
Quan Z. Sheng,Fu‐Sheng Wang,Haihong Huang,Jingjiao Lin,Zhongma Wang,Xiangping Kong,Liangcheng Liu,Wei Tong,Guiyang Cui
标识
DOI:10.1080/21642583.2024.2409116
摘要
Modular Multilevel Converters (MMCs) play a crucial role in high-voltage DC (HVDC) systems due to their adaptable control and swift response capabilities. However, AC side faults could introduce asymmetric double-line frequency components into the MMC's circulating current, jeopardizing DC bus stability. Although strategies to mitigate DC side fluctuations are well-established, a detailed comparison of their operational impacts remains unexplored. The operational effects of MMCs under AC side faults are firstly examined in this study, including issues related to grid-connected current asymmetry and DC bus current fluctuations. Subsequently, two targeted control schemes are devised based on the goals of suppressing the double-line frequency components and only the zero-sequence components of circulating current. Through simulation, these approaches are contrasted, delineating their advantages and disadvantages in terms of circulating current suppression, submodules(SMs) capacitance voltage fluctuation, and other performance metrics, which could provide a foundational reference for designing and selecting MMC control strategies under AC side faults.
科研通智能强力驱动
Strongly Powered by AbleSci AI