Yushen Yang,Peng Xu,Guanghui Wang,Xinxin Liu,Dingbiao Wang
标识
DOI:10.1016/j.enbuild.2023.113558
摘要
To analyze the energetic and exergetic performance of the transcritical CO2 air-source heat pump water heating system in the cold region, the numerical model and simulation algorithm are set up and verified with the experiments. Under the low ambient temperature (−15 °C to 0 °C) and water inlet temperature (9 °C), the performance evaluation of the system is investigated using the developed numerical model at different compressor frequency (75, 80 and 85 Hz). The results show that Qgc, COP and ηex decrease by 14.47%, 12.78% and 20.83% respectively as the ambient temperature decreases from 0 °C to −15 °C. The CO2 outlet state of the gas cooler and corresponding slope of isotherms have significant effects on COP and ηex. The COPopt and ηex,opt exist in the system but at different compressor discharge pressures. With the compressor frequency increasing from 75 Hz to 85 Hz, the increase in Qgc is at the cost of a decrease in COP, and COPopt decreases by 5.31%. The effect of the compressor frequency on ηex is different as the compressor discharge pressure elevates. Thus, a suitable operating condition, considering different needs, should be selected in the system operation.