溶解气体分析
变压器
变压器油
配电变压器
工程类
电气工程
石油工程
环境科学
电压
作者
Naris Chattranont,Sakhon Woothipatanapan,Nattachote Rugthaicharoencheep
出处
期刊:
[Institute of Electrical and Electronics Engineers]
日期:2020-10-14
卷期号:: 165-168
被引量:10
标识
DOI:10.1109/icpei49860.2020.9431480
摘要
This paper discusses Dissolved Gas Analysis (DGA) in transformer oil from two 69/24 kV 24/32 MVA installed in urban areas. By detecting unusual increasing gas, then transformer oil samples were collected frequently according to Standards. First transformer was failed by inside short circuit. All loads were transfer to second transformer. The risk of failure on last transformer is very high. Standards used for DGA interpretation is IEEE C57.104. Evaluation of fault type used Key gas method, Doernenburg ratio, Rogers ratio and Duval Triangle.
科研通智能强力驱动