The DC interconnection project from Qinghai to Tibet is planned to be located above the altitude of 2 880 m with the highest of 5 300 m. To ensure the safe operation of the interconnection project, the flashover voltage of the air gaps on the line tower and in the converter station devices should be revised with the consideration of altitude, or altitude correction factors should be reconsidered. In this paper the altitude correction factors were given by analyzing and comparing some test data obtained at the different altitude areas such as Beijing, Kunming, Xining, Dawu in Qinghai province and Yangbajing in Tibet autonomous region with common altitude correction methods. On the basis of above research results, and under the condition that switching overvoltage was below 1.7 pu and the altitude was from 3 000 m to 5 300 m, the minimum air gaps on the line tower and in the converter stations for DC interconnection project from Qinghai to Tibet were suggested with the rated voltage of ±400 kV and ±500 kV.