Zhe Zhang,Baolian Niu,Zhongbin Zhang,Min Shi
摘要
Abstract Improving the utilization efficiency of cold airflow in data center (DC) has already attracted widespread concern. A broad consensus has been reached that cold/hot‐aisle containment technologies can reduce the mixture of cold and hot air to weaken the overheating phenomenon of the rack in a certain extent. However, local hot spots still occur in the front racks due to lower tile flow rate at the entrance of the cold aisle, which means the thermal environment of front racks can be further improved to achieve the more uniform airflow distribution horizontally and vertically in DC. In this paper, an innovative method of airflow optimization applying jet fans in the cold aisles is proposed to make up the lower tile flow rate, adjust the flow path of cold air from the perforated tiles to racks, and balance temperature heterogeneity. In addition, inductive velocity, nozzle height, horizontal position, and attachment distance of jet fans are optimized to explore the optimal parameters. Results show that the incorporation of jet‐induced ventilation can effectively improve the cooling performance and overall thermal environment in DC, while the amount of IT equipment that exceeded the ASHRAE recommended supply air temperature (SAT) is reduced by about 38%. The jet fan with optimal parameters has a broad application space in the raised floor DC.