Jacek Rybarz,S. Borucki,Michał Kunicki,Aneta Kucińska-Landwójtowicz,Dawid Wajnert
出处
期刊:Energies
[MDPI AG]
日期:2022-06-08
卷期号:15 (12): 4216-4216
被引量:3
摘要
This article proposes a method to modify the construction of a medium voltage (MV) heat shrinkable cable termination in cases of atypical damage to the shields of cross-linked polyethylene (XLPE) insulated cables. The proposed solutions include a modified method of assembling electric field control coating. An attempt was made to check the effect of such damage to the shields of MV cables with XLPE insulation on the level of occurrence of partial discharges within the cable termination. The investigations included testing the XRUHAKXS 1 × 240/25 cable type using the electric method (ME) and high frequency (HF) method with sinusoidal AC test voltage. As a result of the measurements, the values of total charges in the period and phase-resolved partial discharge (PRPD) patterns were obtained. The presented experimental results show the influence of the damage of the semiconducting coating surface on the occurrence of a defect in the cable termination without a modified method of control mantissa pinning. We suggest new methods of assembling MV cable accessories in the case of the presented coating damage in MV cable insulation.
科研通智能强力驱动
Strongly Powered by AbleSci AI