Masoud Noori,Reza Effatnejad,Payman Hajihosseini
标识
DOI:10.1049/iet-gtd.2017.0028
摘要
One of the most important tools for condition monitoring is the gas chromatography test of transformer oil, which is known as dissolved gas analysis (DGA). In this research, the DGA results of >3000 power transformers operating in Iran's power grid were carefully studied and from among them, the results related to transformers suspicious of being faulty were used to validate the fault detection accuracy of the presented fuzzy inference system (FIS). In most of the previously published papers, the detection and isolation of transformer faults has been based on one or two of the following parameters: absolute concentrations of free and dissolved gases in transformer oil, total dissolved combustible gases, total combustible gases, ratios of some gases to each other, and the rates of gas increase. However, in this research, most of these parameters have been used for fault detection and isolation, according to the IEC 60599 standards. Also, no attempt has been previously made to detect the decomposition of insulation papers of transformers; but the presented FIS is able to detect this fault as well. The overall performance accuracy of the presented system is F 1 = 91.2%, which seems to be a suitable value.