Free cooling is commonly used in data centers to reduce cooling system energy consumption using a water-side economizer (WSE). In this system, cooling mode is switched when wet bulb temperature ( T w b ) reaches switchover temperature ( T s w ), and the cooling tower fans are controlled to maintain a specified cooling water approach temperature ( T a p p ). Typically, both T s w and T a p p values are fixed. However, under part load conditions, T s w and T a p p can be optimized to maximize the system performance and save energy. Currently, there are few appropriate methods available to optimize T s w and T a p p in partial-free cooling mode for data centers with WSE. Thus, this study presents a model based methodology to optimize T s w and T a p p in different cooling modes. The proposed methodology is verified through a case study based on data of a real operating data center. Comparison between the calculated optimal T s w and T a p p with that derived by simulation demonstrates the satisfactory accuracies of the proposed method. The case study illustrates that when T s w and T a p p are optimized, the cooling system energy consumption can be saved by 10% when cooling load ratio is 0.6.