JinSeok Choi,Tian-Feng Yuan,Se-Hee Hong,Young-Soo Yoon
出处
期刊:Han-gukbangjaehakoenonmunjip
[Korean Society of Hazard Mitigation]
日期:2020-10-29
卷期号:20 (5): 245-254
被引量:7
标识
DOI:10.9798/kosham.2020.20.5.245
摘要
In this study, experimental tests were performed to determine the electromagnetic shielding characteristics of reinforced concrete based on the thickness of concrete and rebar. In addition, the electromagnetic shielding characteristics based on the steel-fiber volume ratio and rebar spacing of fiber-reinforced concrete were evaluated. Concrete showed significant Shielding Effectiveness (SE) in a high-frequency band with increasing thickness, but the rebar exhibited significant SE in the low-frequency band with increasing diameter, decreasing rebar spacing, and increasing layer. The SE increased with the steel fiber volume ratio, and it also increased owing to the decrease in the rebar spacing for 1.5 vol.% steel fibers.