Mahmud H. Ali,Rawand E. Jalal
摘要
Abstract In the present work, an experimental investigation is conducted to address the influence of inner pipe twisting on the overall performance of a double pipe heat exchanger. With the fluid to fluid heat exchange, both parallel and counter flow directions are examined as well. In addition to the original elliptical pipe, three pipes with different numbers of twisting (3, 5, and 7 twists per unit length) constructed from the elliptical pipe are considered where the heat transfer rate and pressure drop are addressed. All tests are carried out in the turbulent flow regime where the Reynolds number ( Re ) ranging from 5000 to 26,000 and water is used as the working medium. The obtained outcomes show that for both flow directions, there is an enhancement in the heat exchanger overall performance with all considered twisting pipes. The maximum enhancement in the Nusselt number is found to be 1.8 for the parallel flow and around 2.2 for the counter flow compared with the original pipe. The inner pipe with 7 twists, however, improves the overall performance the most, where a maximum performance enhancement factor of 1.63 and 1.9 are observed at Reynolds number of 26,000 in the parallel and counter flow configurations, respectively.