材料科学
压力降
管(容器)
热交换器
鳍
同心管换热器
传热
复合材料
管壳式换热器
机械
热力学
物理
作者
Ji-Hyun Myong,Byung-Nam Choi,Min-Geon Go,Nae-Hyun Kim
标识
DOI:10.1080/08916152.2021.1906357
摘要
It is well known that the replacement of round tubes to oval tubes in a fin-and-tube heat exchanger reduces the air-side pressure drop as well as the low-performance region behind the tube, which improves the thermal performance of the heat exchanger. However, experimental evidences are lacking, especially for generic heat exchangers. In this study, generic heat exchangers having oval tubes were tested, which included two different oval tube dimension and two different tube pitches. Round tube samples were also tested for a comparison purpose. The effect of fin pitch on j factor was negligible, whereas f factor increased as the fin pitch increased. Furthermore, both the j and f factor decreased as the number of tube row increased. A thermal performance comparison based on the ratio of thermal conductance per unit volume (ηohoAo/Vo) to pressure drop per unit length (ΔP/L) revealed that the oval tube samples yielded a higher performance than the round tube samples, except at a small number of tube row. Furthermore, the best performance was obtained from the oval tube samples having a smaller diameter tube. On the other hand, relatively poor performance was obtained from the oval tube samples having a larger diameter tube, probably due to the large pressure drops. The j and f correlations were developed based on the data.
科研通智能强力驱动