Bingyu Mo,Shanghu Zhou,Min Su Han,Pengsheng Xie,Chenxi Li,Xiao Han,Quanlei Qu,Jianwu Li,Ke Chen
摘要
Abstract The water vapor in the ambient air affects the accuracy of the photoacoustic (PA) dissolved gas analysis system for transformer health monitoring. A laser PA system was evaluated by dry and humidified standard gases to study the influence of water vapor concentration on PA gas detection. Theoretical analysis was conducted on the effect of gas molecule relaxation on PA signal detection. A high‐frequency resonant PA cell and a low‐frequency nonresonant PA cell were used to detect acetylene (C 2 H 2 ) and carbon monoxide (CO), respectively. The experimental results show that the PA signal of humidified CO is about 12 times higher than PA signal of dry gas for the resonant PA detection system, respectively. In addition, as the frequency is increased from 30 to 980 Hz, the PA signals of humidified and dry CO attenuate by 1.5 and 6.9 times, respectively.