作者
Victor Dmitriev,Rodrigo M. S. de Oliveira,Fernando S. Brasil,Paulo R. Moutinho de Vilhena,Jonathas F. M. Modesto,Ronaldo F. Zampolo
标识
DOI:10.1590/2179-10742015v14i2526
摘要
Abstract In order to measure electrical signals produced by partial discharges in hydrogenerators stator windings, capacitive couplers are regularly used. They are electrically connected to the windings and therefore, require undesired insulation intrusion. For avoiding such an intrusion, a microstrip directional coupler is used, which is experimentally and numerically investigated in this work. This electromagnetic field sensor is analyzed initially via computer simulation using the finite-difference time-domain method. This numerical analysis is fulfilled considering the coupler placed over a stator bar. Experimental high-voltage tests with generator windings were also performed. We compare the results of the measurements obtained by using various sensors and show that the microstrip directional coupler has some important advantages over traditional capacitive sensors such as complete conductive insulation from the windings and the capacity of detecting shorter PD pulses due to their wider bandwidth.