摘要
In most fire-rated door systems, emphasis is primarily placed on the door shutter, while the contribution of the door frame to overall fire performance is often overlooked. This study investigates the fire resistance of composite timber door frames reinforced with calcium silicate (Cal-Sil) boards of varying thicknesses. Timber sections with densities ranging from 400 to 800 kg/m³ were combined with 6, 9, and 12 mm Cal-Sil barriers and evaluated through furnace exposure, post-fire mechanical testing, and full-scale fire resistance tests. Performance parameters included mass loss, char depth, burning rate, residual compressive strength, screw-withdrawal strength, delamination behaviour, effectiveness of adhesive bonding and mechanical fastening, etc. Results showed significant effects of timber density (p = 0.004), barrier thickness (p = 0.001), and their interaction (p = 0.02) on fire performance. Full-scale testing indicated that unprotected timber frames failed after approximately 50 min, whereas frames protected with 6 and 9 mm Cal-Sil barriers achieved fire resistance ratings of about 90 and 120 min, respectively. Regression analysis revealed that fire endurance increased by approximately 7.6 min for each millimetre increase in barrier thickness (R² = 0.993). A 9 mm Cal-Sil barrier combined with medium-density timber and mechanical fastening provided the optimum performance.