Xiaoqiang Guo,Senyu Du,Naizhe Diao,Changchun Hua,Frede Blaabjerg
标识
DOI:10.1109/tpel.2023.3274911
摘要
Unbalanced loads are general in uninterruptible power supply (UPS), standalone power generation applications and the failure mode of three-phase inverters. Three-phase four-leg inverters are a well-known solution to handle neutral currents caused by unbalanced loads. In four-leg inverters, three-dimensional (3-D) space vector modulation (3DSVM) is widely used. However, the 3DSVM of four-leg current source inverter (CSI) has not been systematically studied so far. To fill this gap, this article proposes a 3DSVM for CSI. The definition of the current vector, the identification of the position of reference vector and the sequence of switches are introduced. Under unbalance loads, the symmetrical load voltage can be realized, which complies with IEEE Std. 1159–2019. The output current can comply with IEEE Std. 519–2014. The proposed 3DSVM has the potential to extend the advanced modulation strategies that have been implemented/ proposed on three-leg CSI.