Yoshimichi Ohki,Naoshi Hirai,Kosuke Sato,Yasuhiro Tanaka
标识
DOI:10.1109/tdei.2024.3355871
摘要
Cables installed in a boiling-water nuclear power plant were removed from three places. The electrical insulation performance of their flame-retardant ethylene-propylene-diene rubber insulation was examined by the current integration method. Namely, the electric charge stored in a measuring capacitor set in series with the sample cable was measured when a high DC voltage was applied. The ratio of the charge stored in the capacitor in the whole period of voltage application to the initial one was found to be a direct indicator of the leakage resistivity of cable insulation. The resistivity was measured much lower when a part of the cable sample was heated to 80 °C than when the whole length was kept at room temperature. This means that the heating-assisted current integration method can be a tool for locating deteriorated positions in the cable insulation. It has also become clear that the cables removed from the three places possess high enough insulation resistivity.