Ge Wang,Yi Zhou,Jingfeng Zhu,Shaoqing Chen,Tao Su,Zhao Jingwei,Wei Liang
标识
DOI:10.1088/1742-6596/1732/1/012181
摘要
Abstract To reveal the real causes of two explosion faults of potential transformer (PT) on a substation connecting to PV plant, an on-line monitoring equipment with a sampling rate of 40 MS/s for the transient voltage was installed on the secondary side of the PT. By switching the 35kV bus bar onto the main transformer, the switching transient processes on the PT were obtained. The field measured transient process indicated that the switching transient voltage caused by switch operation induced the resonance between the charging circuit and the PT and the resonance may be the direct cause of the PT explosion. The effective measures to suppress resonance in this substation are proposed.