Accelerated Aging Tests of 69-kV Cross-Linked Polyethylene Cable and Joints
作者
James L. Williams,Aldo Zanona,Alfred R. Lee
出处
期刊:IEEE Transactions on Power Apparatus and Systems [Institute of Electrical and Electronics Engineers] 日期:1969-02-01卷期号:PAS-88 (2): 157-170被引量:11
标识
DOI:10.1109/tpas.1969.292417
摘要
Test evaluation of 69-kV cross-linked polyethylene (XLPE) cable and joints for use with such cable is described. Joints suitable for connecting together either lengths of 69-kV cross-linked polyethylene (XLPE) cable or XLPE cable to solid-type paper insulated 69-kV cable are studied. It is shown that the characteristics of the tape selected greatly influence the performance of the joint. The thermal resistivity and the thermal expansion of cross-linked polyethylene are also examined.